JMP Equipment Company
  • Home
  • Hydronics Overview Pumping Variable Speed Pump Control Air Control Hot Water Boilers Hydronic Balance Cooling Towers Hydronic Piping
  • Plumbing Overview Domestic Hot Water Recirculation Commercial Sewage Lift Stations Hydropneumatic Tanks Legionella Pressure Booster Sizing
  • Steam Overview Steam Basics Steam Properties Superheated Steam
  • Humidification
  • Technical Manuals Videos White Papers
  • Series Intro Air Management and Pressurization Avoiding Pump Cavitation in Open Systems Series Boiler Installation Pitfalls Series Commercial Sewage Lift Stations Condensing Boiler Plant Piping Cooling Tower and Condenser Water Design Data Center Cooling and Water Efficiency Series Decarbonization with WSHPs Series Domestic Hot Water Recirculation Domestic Water Pressure Booster Sizing Series Energy Efficient Hot Water Boiler Plant Design Fire Pumps for Sprinkler Systems Series Geothermal Well Drilling Series High Volume Low Speed Fan Series How to Build a Centrifugal Pump Curve Series How To Develop Cooling Tower Life Cycle Cost Series How to Pick a Centrifugal Pump Series How to Pick a Cooling Tower Series How to Read a Pump Curve Humidification Basics Series Hydronic Balancing Series Hydronic Systems Series Modern Pump Selection Series Parallel Optimized Pumps Series Parallel Pumping in Condenser Water Applications Series Part Load Efficiency Values Series Pump Efficiency Standards Series Pump Motor Efficiency Series Pump Optimization Series Reducing Virus Transmission With Humidification Series Steam Basics Series Steam System Series Understanding Primary Secondary Pumping Variable Primary Chilled Water Series Variable Speed Pump Control Series Wastewater Heat Recovery Series Waterside Economizing Series Water Source Heat Pump Introduction Series Water Source Heat Pump System Design Series Water Source Heat Pump Control Series
  • jmpco.com
JMP Equipment Company
  • Home/
  • Hydronics/
    • Hydronics Overview
    • Pumping
    • Variable Speed Pump Control
    • Air Control
    • Hot Water Boilers
    • Hydronic Balance
    • Cooling Towers
    • Hydronic Piping
  • Plumbing/
    • Plumbing Overview
    • Domestic Hot Water Recirculation
    • Commercial Sewage Lift Stations
    • Hydropneumatic Tanks
    • Legionella
    • Pressure Booster Sizing
  • Steam/
    • Steam Overview
    • Steam Basics
    • Steam Properties
    • Superheated Steam
  • Humidification/
  • White Papers/
    • Technical Manuals
    • Videos
    • White Papers
  • Series/
    • Series Intro
    • Air Management and Pressurization
    • Avoiding Pump Cavitation in Open Systems Series
    • Boiler Installation Pitfalls Series
    • Commercial Sewage Lift Stations
    • Condensing Boiler Plant Piping
    • Cooling Tower and Condenser Water Design
    • Data Center Cooling and Water Efficiency Series
    • Decarbonization with WSHPs Series
    • Domestic Hot Water Recirculation
    • Domestic Water Pressure Booster Sizing Series
    • Energy Efficient Hot Water Boiler Plant Design
    • Fire Pumps for Sprinkler Systems Series
    • Geothermal Well Drilling Series
    • High Volume Low Speed Fan Series
    • How to Build a Centrifugal Pump Curve Series
    • How To Develop Cooling Tower Life Cycle Cost Series
    • How to Pick a Centrifugal Pump Series
    • How to Pick a Cooling Tower Series
    • How to Read a Pump Curve
    • Humidification Basics Series
    • Hydronic Balancing Series
    • Hydronic Systems Series
    • Modern Pump Selection Series
    • Parallel Optimized Pumps Series
    • Parallel Pumping in Condenser Water Applications Series
    • Part Load Efficiency Values Series
    • Pump Efficiency Standards Series
    • Pump Motor Efficiency Series
    • Pump Optimization Series
    • Reducing Virus Transmission With Humidification Series
    • Steam Basics Series
    • Steam System Series
    • Understanding Primary Secondary Pumping
    • Variable Primary Chilled Water Series
    • Variable Speed Pump Control Series
    • Wastewater Heat Recovery Series
    • Waterside Economizing Series
    • Water Source Heat Pump Introduction Series
    • Water Source Heat Pump System Design Series
    • Water Source Heat Pump Control Series
  • jmpco.com/
Series Banner Pump Curve.jpg
JMP Equipment Company

How to Build a Centrifugal Pump Curve Series

JMP Equipment Company
  • Home/
  • Hydronics/
    • Hydronics Overview
    • Pumping
    • Variable Speed Pump Control
    • Air Control
    • Hot Water Boilers
    • Hydronic Balance
    • Cooling Towers
    • Hydronic Piping
  • Plumbing/
    • Plumbing Overview
    • Domestic Hot Water Recirculation
    • Commercial Sewage Lift Stations
    • Hydropneumatic Tanks
    • Legionella
    • Pressure Booster Sizing
  • Steam/
    • Steam Overview
    • Steam Basics
    • Steam Properties
    • Superheated Steam
  • Humidification/
  • White Papers/
    • Technical Manuals
    • Videos
    • White Papers
  • Series/
    • Series Intro
    • Air Management and Pressurization
    • Avoiding Pump Cavitation in Open Systems Series
    • Boiler Installation Pitfalls Series
    • Commercial Sewage Lift Stations
    • Condensing Boiler Plant Piping
    • Cooling Tower and Condenser Water Design
    • Data Center Cooling and Water Efficiency Series
    • Decarbonization with WSHPs Series
    • Domestic Hot Water Recirculation
    • Domestic Water Pressure Booster Sizing Series
    • Energy Efficient Hot Water Boiler Plant Design
    • Fire Pumps for Sprinkler Systems Series
    • Geothermal Well Drilling Series
    • High Volume Low Speed Fan Series
    • How to Build a Centrifugal Pump Curve Series
    • How To Develop Cooling Tower Life Cycle Cost Series
    • How to Pick a Centrifugal Pump Series
    • How to Pick a Cooling Tower Series
    • How to Read a Pump Curve
    • Humidification Basics Series
    • Hydronic Balancing Series
    • Hydronic Systems Series
    • Modern Pump Selection Series
    • Parallel Optimized Pumps Series
    • Parallel Pumping in Condenser Water Applications Series
    • Part Load Efficiency Values Series
    • Pump Efficiency Standards Series
    • Pump Motor Efficiency Series
    • Pump Optimization Series
    • Reducing Virus Transmission With Humidification Series
    • Steam Basics Series
    • Steam System Series
    • Understanding Primary Secondary Pumping
    • Variable Primary Chilled Water Series
    • Variable Speed Pump Control Series
    • Wastewater Heat Recovery Series
    • Waterside Economizing Series
    • Water Source Heat Pump Introduction Series
    • Water Source Heat Pump System Design Series
    • Water Source Heat Pump Control Series
  • jmpco.com/

How to Build a Centrifugal Pump Curve Series

Featured
How to Build a Centrifugal Pump Curve Part 5: Net Positive Suction Head
September 25, 2024
How to Build a Centrifugal Pump Curve Part 5: Net Positive Suction Head
September 25, 2024

We are almost finished building our e-1510 pump curve! In this final blog of our series, we’ll introduce positive suction head (NPSH) to our curve and explain what NPSH is and why it matters....

Read more →
September 25, 2024
How to Build a Centrifugal Pump Curve Part 4: Efficiency Curves
September 16, 2024
How to Build a Centrifugal Pump Curve Part 4: Efficiency Curves
September 16, 2024

This blog introduces efficiency curves (islands) to our pump curve and examines the variables impacting pump efficiency. We also introduce a valuable equation for....

Read more →
September 16, 2024
How to Build a Centrifugal Pump Curve Part 3: Motor Selection
September 9, 2024
How to Build a Centrifugal Pump Curve Part 3: Motor Selection
September 9, 2024

In Part 2 of our How to Build a Centrifugal Pump Curve series, we added five head/capacity curves to the e-1510 4BD pump curve we are building. These curves reflect the tested performance of pumps with various-size impellers. Now, it's time to focus on the pump’s power requirement and how it....

Read more →
September 9, 2024

 

  • Home/
  • Hydronics/
    • Hydronics Overview
    • Pumping
    • Variable Speed Pump Control
    • Air Control
    • Hot Water Boilers
    • Hydronic Balance
    • Cooling Towers
    • Hydronic Piping
  • Plumbing/
    • Plumbing Overview
    • Domestic Hot Water Recirculation
    • Commercial Sewage Lift Stations
    • Hydropneumatic Tanks
    • Legionella
    • Pressure Booster Sizing
  • Steam/
    • Steam Overview
    • Steam Basics
    • Steam Properties
    • Superheated Steam
  • Humidification/
  • White Papers/
    • Technical Manuals
    • Videos
    • White Papers
  • Series/
    • Series Intro
    • Air Management and Pressurization
    • Avoiding Pump Cavitation in Open Systems Series
    • Boiler Installation Pitfalls Series
    • Commercial Sewage Lift Stations
    • Condensing Boiler Plant Piping
    • Cooling Tower and Condenser Water Design
    • Data Center Cooling and Water Efficiency Series
    • Decarbonization with WSHPs Series
    • Domestic Hot Water Recirculation
    • Domestic Water Pressure Booster Sizing Series
    • Energy Efficient Hot Water Boiler Plant Design
    • Fire Pumps for Sprinkler Systems Series
    • Geothermal Well Drilling Series
    • High Volume Low Speed Fan Series
    • How to Build a Centrifugal Pump Curve Series
    • How To Develop Cooling Tower Life Cycle Cost Series
    • How to Pick a Centrifugal Pump Series
    • How to Pick a Cooling Tower Series
    • How to Read a Pump Curve
    • Humidification Basics Series
    • Hydronic Balancing Series
    • Hydronic Systems Series
    • Modern Pump Selection Series
    • Parallel Optimized Pumps Series
    • Parallel Pumping in Condenser Water Applications Series
    • Part Load Efficiency Values Series
    • Pump Efficiency Standards Series
    • Pump Motor Efficiency Series
    • Pump Optimization Series
    • Reducing Virus Transmission With Humidification Series
    • Steam Basics Series
    • Steam System Series
    • Understanding Primary Secondary Pumping
    • Variable Primary Chilled Water Series
    • Variable Speed Pump Control Series
    • Wastewater Heat Recovery Series
    • Waterside Economizing Series
    • Water Source Heat Pump Introduction Series
    • Water Source Heat Pump System Design Series
    • Water Source Heat Pump Control Series
  • jmpco.com/

JMP Equipment Company

Search

No results found

Blog Archive

Series

  • Air Management and Pressurization

  • Avoiding Pump Cavitation in Open Systems

  • Boiler Installation Pitfalls Series

  • Commercial Sewage Lift Stations

  • Condensing Boiler Plant Piping Design

  • Cooling Tower and Condenser Water Design

  • Data Center Cooling and Water Efficiency Series

  • Decarbonization with WSHPs Series

  • Domestic Hot Water Recirculation

  • Domestic Water Pressure Booster Sizing Series

  • Fire Pumps for Sprinkler Systems Series

  • Geothermal Well Drilling Series

  • High Volume Low Speed Fan Series

  • Hot Water Boiler Plant Design

  • How to Build a Centrifugal Pump Curve Series

  • How To Develop Cooling Tower Life Cycle Cost

  • How to Pick a Centrifugal Pump

  • How to Pick a Cooling Tower

  • How to Read a Pump Curve

  • Humidification Basics

  • Hydronic Balancing

  • Hydronic Systems Series

  • Modern Pump Selection

  • Parallel Optimized Pump Series

  • Parallel Pumping in Condenser Water Applications

  • Part Load Efficiency Values

  • Pump Efficiency Standards

  • Pump Motor Efficiency Series

  • Pump Optimization Series

  • Reducing Virus Transmission With Humidification Series

  • Steam Basics Series

  • Steam System Series

  • Understanding Primary Secondary Pumping

  • Variable Primary Chilled Water Systems

  • Variable Speed Pump Control

  • Wastewater Heat Recovery Series

  • Water Source Heat Pump Series

  • Waterside Economizing Series

  • WSHP Control Series

  • WSHP System Design Series

  • Check Out Our Videos!

Check Out Videos by JMP Co.

Get Updates from Us

Visit our Contact Page and let us know what information you'd like to receive.

Contact About Videos Sign Me Up

Powered by Squarespace

 

Privacy Policy