Commercial Sewage Lift Stations Part 4 - Pump Types and Control Requirements

By Chris Edmondson

 Pumps used in commercial sewage lift stations come in a variety of types (effluents, grinders, etc.)  To determine which type is right for your application you must answer two questions:

  1. What size solids will have to be pumped?
  2. What is the size of the discharge pipe?

 Simply stated, you can’t pump 2-inch solids through a 1-inch pipe.  If these are the parameters of the application at hand, then a grinder pump is in order to chop the solids into smaller, more manageable pieces. 

 This is but one example of how the pump duty will impact the type of pump you choose.  The various types pumps are listed below, along with the applications for which they are most suited:

Pump Type

Best Suited For….

Sump Pump

Dirty water applications where solids are not typically present and are unlikely to ever exceed 3/8”.

Effluent Pumps

Partially or completely treated wastewater applications with solids of 1” or less.

Sewage Pumps

Commercial sewage applications where solids are 2 ½” or larger.

Vortex Pumps

Applications involving waste that includes long, stringy, and/or fibrous solids.  Examples include raw sewage lift stations, storm water applications, paper mill waste, etc.

Grinder Pumps

Applications where solid size is likely to exceed the size of the discharge pipe.  These pumps have a cutting system made of hardened stainless steel to shear solids so they can pass thru smaller pipe. Also useful in high pressure discharge systems typically associated with groups of homes, motels, schools, shopping centers, etc.

Whatever pump is selected, it should be able to maintain a velocity of 2 to 8 feet of flow per second in order to meet the International Plumbing Code (IPC) requirements (See Table 1).  However, it is always important to check with local plumbing codes, those codes may exceed the IRC requirements.  

PUMPS.jpg

 Table 1

Select Pipe Size and Pump Discharge

 Note:  Maintains velocity of 2 to 8 feet per second

 Your pump model selection will be based on the following:

 -       Flow rate

-       Solid size

-       Pump style

-       TDH

-       Discharge pipe size

-       RPM

Control Matters

All of these details, along with the specific pump selection and control requirements, should be indicated on the drawings.  Control requirements will include the type of Level Controller required for the pump system, along with all following components that are inclusive within the control panel itself:

-       Disconnects

-       Starts with Overload Protection

-       T-O-A (Test-Off-Automatic)

-       Alarm Systems

-       Automatic Pump Rotation

 The basic control requirements vary little from one lift station application to the next, however, the voltage as well as the type of NEMA enclosure required will often vary.  Selection of the latter depends on the location of the panel itself – whether it is indoor, outdoor, etc.  Table 2 shows the various types of NEMA Enclosures used for sewage applications.

 Table 2

NEMA 1

General Purpose Indoor

NEMA 3R

Rainproof Sleet Resistant, Ice Resistant

NEMA 4

Water Tight & Dust Tight – Indoor and Outdoor

NEMA 4X

NEMA 4 with Corrosion Resistant Enclosure

NEMA 7

Hazardous Locations – Indoor – Air Break Equipment

 For more information, check out JMP’s webinar on designing sump and sewage systems.